[Specifications]:4DI + 4DO
[Interface mode]:RS485
[Installation method]:rail
[Size]:145*90mm
[Introduction]:MA01-AXCX4040 supports the acquisition of 4-channel sensor switch input (DI), which is converted to serial port(RS485) and data is transmitted to configuration software or PLC. The serial port I/O networking module (also called "remote IO") that realizes the remote acquisition and control by issuing commands through the serial port to control 4 relay switch outputs (DO)
Serial number | Pin | Pin direction | remarks |
---|---|---|---|
1 | + | Power supply + (8~28V) | Suggest RVV 2*0.75 wire |
2 | ﹣ | Grounding-(8~28V) | Suggest RVV 2*0.75 wire |
3 | B/RX | RS485 corresponding to B | Recommend RVSP 3*0.5 wire |
4 | A/TX | RS485 corresponds to A | Recommend RVSP 3*0.5 wire |
5 | GND | Signal ground | Recommend RVSP 3*0.5 wire |
6 | COM | Input channel common | Recommend RVV 2*0.5 wire |
7 | DI1 | Switch input channel 1 | Recommend RVV 2*0.5 wire |
8 | DI2 | Switch input channel 2 | Recommend RVV 2*0.5 wire |
9 | DI3 | Switch input channel 3 | Recommend RVV 2*0.5 wire |
10 | DI4 | Switch input channel 4 | Recommend RVV 2*0.5 wire |
11 | DO1 | Switch output channel 1 | The relay has normally open and normally closed terminals |
12 | DO2 | Switch output channel 2 | The relay has normally open and normally closed terminals |
13 | DO3 | Switch output channel 3 | The relay has normally open and normally closed terminals |
14 | DO4 | Switch output channel 4 | The relay has normally open and normally closed terminals |