Home >Modem>Remote IO module>Ethernet IO
ME31-XXXA0006 Network I/O Networking Module
ME31-XXXA0006 Network I/O Networking Module
【6AO】ME31-XXXA0006 Network I/O Networking Module

[Communication interface]:RJ45, RS485

[Working voltage]:DC 8 ~ 28V

[Product weight]:135±5 g

[Product size]:121*72*34mm

[Serial port baud rate]:9600bps (customizable)

[Introduction]:ME31-XXXA0006 is a network I/O networking module with 6 analog outputs (0-20mA/4-20mA), supports Modbus TCP protocol or Modbus RTU protocol for acquisition control, and the device can also be used as a simple Modbus gateway (automatically send commands with non-local Modbus addresses through the serial port/network port).

Category Name Parameters
power supplyOperating VoltageDC8~28V
Power indicatorblue LED indication
serial portCommunication InterfaceRJ45, RS485
baud rate9600bps (customizable)
ProtocolStandard Modbus TCP, Modbus RTU protocols
MODBUSdevice addressCan be modified by Modbus command and host computer
AO outputNumber of AO channels6 way
AO output typeCurrent output, 2-wire connection
AO output range0~20mA~20mA
AO resolution16 bit
Output accuracy3‰
output indicationOLED screen display
otherProduct Size121mm * 72mm * 34mm (L*W*H)
product weight135±5g
Working temperature and humidity-40 ~ +85℃, 5% ~ 95%RH (no condensation)
storage temperature and humidity-40 ~ E17+105℃, 5% ~ 95%RH (no condensation)
Installation method  rail installation
Category Name Parameters
Ethernet parametersOperating modeTCP server (up to 4-way client access)
Local IP192.168.3.7
local port502
subnet mask255.255.255.0
gateway address192.168.3.1
DHCPclosure
Native MACDetermined by the chip (fixed)
target IP192.168.3.3
target port502
DNS server114.114.114.114
active uploadclosure
Serial parametersbaud rate9600bps (8 types)
Check methodNone (default), Odd, Even
data bit8
stop bit1
MODBUS parametersModbus master-slaveSlave
address1